Salicru's SLC 1000 TWIN PRO2 1000VA UPS tower is equipped with on-line double-conversion technology and the latest features to make it an advanced protection system for sensitive and critical loads.
High output power factor (PF=0.9) ensures availability to all types of loads, full control through status information via LCD display and keypad, extensive monitoring and communication options via the built-in USB HID interface, an intelligent slot for SNMP cards or relays and a wide range of software packages. Free monitoring version downloadable for Windows, Linux, Unix or Mac and packages available for multi servers or virtualised systems.
For facilities that require more back-up time, there is a possibility of backup extensions using UPSs with extra charger and additional battery modules. Also notable is the possibility of Eco-mode operation to improve the efficiency of the device, EPO (emergency power off) functions, operation as a frequency converter and built-in battery test.
Features
1000 VA of Power
4 x C13 IEC outlet sockets
On-line double-conversion technology.
Output power factor PF=0.9.
Control panel with LCD screen and keypad.
Tower format.
Backup extensions available for all power ratings.
UPS models with extra charger for backup extensions.
USB HID interface for all models as standard.
Downloadable monitoring software for Windows, Linux, Unix and Mac.
Intelligent slot for SNMP/relays.
Eco-mode operation.
Automatic frequency detector.
Frequency conversion function. EPO – emergency power off.
Manual and/or automatic programmable battery test.
Smart battery charger to shorten average recharging times.
Battery recharging with device turned off.
SLC Greenergy solution.
Applications
Power supply failures in IT systems can cause losses as a result of downtime and the time taken to restore the system to normal operation, and damage to network hardware. Many other disturbances (micro power outages, voltage fluctuations, frequency variations, harmonics, transients, etc.) can also cause IT environments to malfunction.
Display
Level of battery available.
Level of load connected.
Operation/alarm/fault status.
Input voltage and frequency.
Output voltage and frequency.
Settings mode.
Communications
USB HID UPS: Enables control, parameter configuration and computer shutdown/ hibernation via the USB port. Available with Windows, Linux for Mac. UPS monitoring and management software for closing files/applications in Windows, Linux, Unix and Mac environments. Free and downloadable from Salicru.
Intelligent slot for connecting SNMP or optocoupler cards.
Salicru Warranty
Online registration at Salicru.
2-year warranty.
Batteries covered by the warranty.
Telephone technical support.
Technical Specification
MODEL
SLC 1000 TWIN PRO2
UPS Power (VA / W)
1000 / 900
Technology
On-line double-conversion
Format
Tower
Ports
AC outlets
4 x power IEC 60320 C13
AC outlet type
IEC 60320 C13
Input
Rated Voltage
220 / 230 / 240 V
Voltage range 100% load
176 - 300V
Voltage range 40% load
100 - 300V
Power Factor
≥0.99
Frequency
50 / 60 Hz ±10%
Input protection
Resettable breaker
Output
Rated voltage
220 / 230 / 240 V
Voltage accuracy (battery mode)
±1%
Waveform (battery mode)
Pure sinusoidal
Total harmonic distortion (THDv)
<2%
Synchronous range
±10%
Battery mode frequency accuracy
±0.05 Hz
Synchronous speed
1 Hz/s
Performance
On-line
>89% ÷ 92%
Eco-mode
>98%
Admissible
overloads
On-line mode
105% constant / 130% for 60 s / 150% for 10 s
Battery mode
105% constant / 130% for 10 s / 150% for 1 s
Bypass mode
130% constant / 180% for 60 s
Battery
Battery type
Pb-Ca sealed, AGM, maintenance-free
Protection
Against power surges, undervoltages and alternating current components
Battery test
Manual and/or automatic programmable
Charging
Charge type
I/U (constant current/constant voltage)
Recharge time
4 hours to 90%
Communication
Interface
USB (HID protocol)
Slot for SNMP/relays
Yes
Downloadable monitoring software
For Windows, Unix, Linux and Mac
Operating Modes
On-line double-conversion
Yes
Eco-mode
Yes
Frequency converter (CVCF)
Yes, Up to 60% of the load
General
Operating temperature
0ºC - 40ºC
Relative humidity
Up to 95%, non-condensing
Noise level at 1 metre
≤49 dB (100% load) / ≤41 dB (60% load)
Dimensions (D x W x H mm)
356 x 144 x 228
Weight
10.20Kg
Standards
Safety
EN 62040-1:2008+A1:2013
Electromagnetic compatibility (EMC)
EN 62040-2
Operation
VFI in accordance with EN 62040-3
Quality & Environmental Management
ISO-9001 and ISO-14001