Enhanced protection for mid-range systems with single-phase power supply
Salicru's SLC 4000 TWIN PRO2 4kVA UPS features on-line double conversion technology, currently the most advanced for the protection of critical systems as it provides a fully stabilised and filtered sinusoidal supply voltage.
The Salicru SLC TWIN PRO2's output voltage is always single-phase, featuring a single-phase input of 4 kVA. The SLC 4000 TWIN PRO2 4kVA UPS provides a unitary output power factor, the most optimum for systems and environments with high energy needs. Adaptability is another important feature thanks to the numerous operating modes available: On-line, Batteries, Eco-mode, Bypass, Frequency converter and Parallel redundant.
The possibilities of control and monitoring are varied: on the one hand, an LCD display + keypad for local operation of the device, and, on the other, various communication options (USB HID and RS-232 interfaces, and slot for SNMP, RS-485 and AS-400 cards) that enable the UPS to be integrated into standard or virtualised platforms for management, incident notification and remote maintenance.
Features
On-line double conversion and DSP control technology.
Output power factor PF=1
Compact tower format for space saving.
Active power factor corrector for all input phases.
Multiple operating modes for better adaptability.
Equipped for parallel operation as standard, up to 3 devices.
USB and RS-232 interface for all models as standard.
Monitoring software for Windows, Linux, Unix and Mac.(downloadable)
Intelligent slot for SNMP/RS-485/optocoupler cards.
Eco-mode operation for increased efficiency.
Backup extensions available for all power ratings.
Frequency conversion function.
EPO – emergency power off.
Manual and/or automatic programmable battery test.
SLC Greenergy solution.
Operating Modes
On-line double-conversion
Double voltage conversion (AC/DC + DC/AC), providing the best degree of safety to loads
Batteries
In the event of power failure, the loads continue to be powered by means of batteries
Bypass
In the event of any eventuality (incident, overload, etc.), the loads continue to be powered by the input voltage.
Frequency Converter
Adaptation of the output frequency to the needs of the load (50/60 Hz or 60/50 Hz).
Eco-Mode
Increased efficiency up to 99%, with immediate availability of full power.
Parallel Redundant
Increased safety (N+1) or capacity, with configurations of up to 3 devices.
Applications
Salicru's SLC TWIN PRO2 series is the best option for providing a secure power supply to ERP systems, Business Intelligence, CRM solutions, intranets/extranets and corporate networks in the event of a wide range of possible disturbances (micro power outages, voltage fluctuations, frequency variations, harmonics, transients, etc.), which can cause irreparable damage or incur high costs in all of these critical systems.
Comparison Chart
Technical Specification
MODEL
SLC 4000 TWIN PRO2
UPS Power (VA / W)
4000 / 4000
Technology
On-line, double conversion, PFC with double DC bus
Format
Tower
Input
Rated Voltage
208 / 220 / 230 / 240 V (1)
Voltage range
110 ÷ 276 V (2)
Total harmonic distortion (THDi)
<4%
Power Factor
≥0.99
Frequency
50 / 60 Hz ±10%
Input protection
Resettable breaker
Output
Rated voltage
208 / 220 / 230 / 240 V (1)
Voltage accuracy (battery mode)
±1%
Power factor
1
Total harmonic distortion (THDv)
≤1% linear load;
≤4% non-linear load
Performance (normal mode)
93% ÷ 94%
Permissible overloads
(normal mode)
Up to 110% for 10 min;
130% for 1 min
Parallel
Yes, up to 3 units (3)
Synchronisation
with mains
±4 Hz
without mains
±0.1 Hz
Programmable priority outputs
No
Crest factor
3 to 1
Manual Bypass
Yes
Bypass
Type
Hybrid
Transfer time
Nil
Battery
Battery type
Pb-Ca sealed, AGM, maintenance-free
Protection
Against power surges, undervoltages and alternating current components
Charging
Charge type
I/U (constant current/constant voltage)
Recharge time
7-9 hours to 90%
Temperature voltage compensation
Yes
Communication
Interface
USB, RS-232 and relay
Intelligent slot
Yes, ready for SNMP / AS400 / RS485-Modbus
Downloadable monitoring software
For Windows, Unix, Linux and Mac
Other Functions
Eco-mode 4
Yes
Frequency converter
Yes (4)
Cold start
Yes
General
Operating temperature
0ºC - 40ºC
Relative humidity
Up to 95%, non-condensing
Noise level at 1 metre
Less than 60dB
Dimensions (D x W x H mm)
592 x 250 x 576
Weight
81Kg
Standards
Safety
EN 62040-1; EN 60950-1
Electromagnetic compatibility (EMC)
EN 62040-2 Category C3
Operation
VFI in accordance with EN 62040-3
Quality & Environmental Management
ISO-9001 and ISO-14001
(1) Power reduction to 90% for 208 V input
(2) With 50% load
(3) Power reduction to 90%